The issue | The solution | The outcome

Yahoo! approached Dataracks to look at ways to eliminate hot spots and improve the life expectancy and efficiency of its London datacentres. Work on the first three aisle pilot project started in June 2007.
“A datacentre operates 24/7 and as
any minor outage would create huge
consequences for the end clients we
have built considerable redundancy
into our facility. This includes a
spare cooler for every two in operation
and keeping the temperature lower
than required to allow for variation.”
European Datacentre Operations Manager,
Yahoo!
After an environmental assessment, Dataracks identified the problems with airflow through the aisles of the datacentre and designed an innovative solution to rectify the issues.
Following the success of the pilot project the trial was expanded to the full room (200 racks), resulting in continued improved temperature management in the datacentre and significant reduction in energy consumption.
The aisles were noticeably colder in less than an hour of the solution being implemented. As it proved possible to maintain temperatures in the cold aisle consistently, the data manager felt confident in reducing the cooling, raising inlet temperature to 20°C from 14°C with further rises being implemented. Hot air return temperatures increased, creating a greater temperature differential, which improved CRAC efficiency
The drop in energy usage attracted interest from the Datacentre property owner (who will be implementing the solution across their Datacentres throughout Europe.)
“When Dataracks installed the eCool Cold Aisle Containment we noticed the difference within an hour. The temperature reduced and has kept the cold aisle consistent within 2-3°C. This has enabled us to balance the cooling system, put two of the eleven CRAC units onto standby and cut energy consumption by 15%.” European Datacentre Operations Manager, Yahoo!